NENSYS HOME
>
AC/DC INVERTERS
> SPECIFICATIONS [
LS SERIES
/
IRM SERIES
]
LATRONICS LS SERIES SPECIFICATIONS
Updated Sept 06
www.nensys.com.au
LS-512
LS-624
LS-648
LS-6110
LS-6125
LS-1012
LS-1224
LS-1248
LS-12110
LS-12125
LS-1512
LS-1824
Nominal battery voltage
12 V
24 V
48 V
110 V
125 V
12 V
24 V
48 V
110 V
125 V
12 V
24 V
Input voltage range
10.5-17 V
21-34 V
42-68 V
80-140 V
96-160 V
10.5-17 V
21-34 V
42-68 V
80-140 V
96-160 V
10.5-17 V
21-34 V
Standby current
27 mA
22 mA
19 mA
16 mA
15 mA
37 mA
28 mA
22 mA
18 mA
17 mA
42 mA
30 mA
Inverter ON - no load
0.42 A
0.31 A
0.18 A
0.15 A
0.14 A
0.45 A
0.25 A
0.19 A
0.15 A
0.14 A
0.67 A
0.32 A
Continuous output
500 W
600 W
600 W
600 W
600 W
1000 W
1200 W
1200 W
1200 W
1200 W
1500 W
1800 W
1/2 hour rating
550 W
750 W
750 W
750 W
750 W
1150 W
1600 W
1600 W
1600 W
1600 W
1600 W
2200 W
5 sec surge rating
1500 W
2000 W
2000 W
2000 W
2000 W
3000 W
3600 W
3600 W
3600 W
3600 W
4500 W
5400 W
Output voltage
230Vz
4%
Frequency
50Hz
0.1%
Waveshape
True Sinewave
Total harmonic distortion
<4%
Peak efficiency
90%
92%
93%
93%
93%
91%
92%
94%
94%
94%
91%
94%
Protection circuitry
overtemperature, overload / short circuit, battery undervoltage, battery overvoltage
Autostart sensitivity
0 - 20W adjustable
Power factor
All conditions
Width
260 mm
330 mm
Height
160 mm
296 mm
Depth
100 mm
150 mm
Weight
5.5 kg
5.5 kg
5.5 kg
4.7 kg
4.7 kg
11 kg
11 kg
11 kg
11 kg
11 kg
14 kg
14 kg
1) Ratings at 25degC, nominal battery voltage and unity power factor.
2) Specifications subject to change without notice.
LATRONICS LS SERIES SPECIFICATIONS ( Con't )
Updated Sept 06
www.nensys.com.au
LS-1848
LS-18110
LS-18125
LS-2012
LS-2324
LS-2548
LS-3024
LS-3548
LS-4024
LS-5048
LS-7048
Nominal battery voltage
48 V
110 V
125 V
12 V
24 V
48 V
24 V
48 V
24 V
48 V
48 V
Input voltage range
42-68 V
80-140 V
96-160 V
10.5-17 V
21-34 V
42-68 V
21-34 V
42-68 V
21-34 V
42-68 V
42-68 V
Standby current
24 mA
18 mA
17 mA
75 mA
45 mA
35 mA
50 mA
40 mA
60 mA
55 mA
60 mA
Inverter ON - no load
0.26 A
0.21 A
0.19 A
1.1 A
0.51 A
0.3 A
0.6 A
0.33 A
1.1 A
0.48 A
0.5 A
Continuous output
1800 W
1800 W
1800 W
2000 W
2300 W
2500 W
3000 W
3500 W
4000 W
5000 W
7000 W
1/2 hour rating
2200 W
2200 W
2200 W
2200 W
2800 W
3000 W
3700 W
4100 W
4500 W
6000 W
8500 W
5 sec surge rating
5400 W
5400 W
5400 W
6000 W
7000 W
7500 W
9000 W
10500 W
12000 W
15000 W
20000 W
Output voltage
230V
4%
Frequency
50Hz
0.1%
Waveshape
True Sinewave
Total harmonic distortion
<4%
Peak efficiency
94%
94%
94%
90%
94%
94%
93%
94%
94%
95%
95%
Protection circuitry
overtemperature, overload / short circuit, battery undervoltage, battery overvoltage
Autostart sensitivity
0 - 20W adjustable
Power factor
All conditions
Width
330 mm
370 mm
475 mm
Height
296 mm
386 mm
458 mm
Depth
150 mm
180 mm
187 mm
Weight
14 kg
14 kg
14 kg
22 kg
22 kg
22 kg
24 kg
24 kg
30 kg
30 kg
34 kg
1) Ratings at 25degC, nominal battery voltage and unity power factor.
2) Specifications subject to change without notice.
PAGE TOP
BACK TO LATRONICS INVERTERS MAIN PAGE
LATRONICS IRM SERIES SPECIFICATIONS
Updated Sept 06
www.nensys.com.au
IRM 512
IRM 624
IRM 648
IRM 696
IRM 6120
IRM 1012
IRM 1224
IRM 1248
IRM 1296
IRM 12120
IRM 1512
IRM 1824
IRM 1848
Nominal battery voltage
12 V
24 V
48 V
96 V
120 V
12 V
24 V
48 V
96 V
120 V
12 V
24 V
48 V
Input voltage range
10-17 V
21-34 V
42-68 V
80-140 V
96-160 V
10-17 V
21-34 V
42-68 V
80-140 V
96-160 V
10-17 V
21-34 V
42-68 V
Standby current
27 mA
22 mA
19 mA
16 mA
15 mA
37 mA
28 mA
22 mA
18 mA
17 mA
42 mA
30 mA
24 mA
Inverter ON - no load
0.42 A
0.31 A
0.15 A
0.14 A
0.13 A
0.45 A
0.25 A
0.15 A
0.14 A
0.13 A
0.67 A
0.32 A
0.18 A
Continuous output
500 W
600 W
600 W
600 W
600 W
1000 W
1200 W
1200 W
1200 W
1200 W
1500 W
1800 W
1800 W
1/2 hour rating
550 W
750 W
750 W
750 W
750 W
1150 W
1600 W
1600 W
1600 W
1600 W
1600 W
2200 W
2200 W
5 sec surge rating
1500 W
2000 W
2000 W
2000 W
2000 W
3000 W
3600 W
3600 W
3600 W
3600 W
4500 W
5400 W
5400 W
Output voltage
230V
4%
Frequency
50Hz
0.1%
Waveshape
True Sinewave
Total harmonic distortion
<4%
Peak efficiency
90%
92%
93%
93%
93%
91%
92%
94%
94%
94%
91%
94%
94%
Protection circuitry
overtemperature, overload / short circuit, battery undervoltage, battery overvoltage
Autostart sensitivity
0 - 20W adjustable
Power factor
All conditions
Height
3U
Depth
350 mm
Weight
7 kg
7 kg
7 kg
7 kg
7 kg
12 kg
12 kg
12 kg
12 kg
12 kg
16 kg
16 kg
16 kg
1) Ratings at 25degC, nominal battery voltage and unity power factor.
2) Specifications subject to change without notice.
LATRONICS IRM SERIES SPECIFICATIONS ( Con't )
Updated Sept 06
www.nensys.com.au
IRM 1896
IRM 18120
IRM 2012
IRM 2324
IRM 2548
IRM 2596
IRM 25120
IRM 3024
IRM 3548
IRM 3596
IRM 35120
IRM 5048
Nominal battery voltage
96 V
120 V
12 V
24 V
48 V
96 V
120 V
24 V
48 V
96 V
120 V
48 V
Input voltage range
80-140 V
96-160 V
10-17 V
21-34 V
42-68 V
80-140 V
96-160 V
21-34 V
42-68 V
80-140 V
96-160 V
42-68 V
Standby current
18 mA
17 mA
75 mA
45 mA
35 mA
24 mA
22 mA
50 mA
40 mA
28 mA
26 mA
55 mA
Inverter ON - no load
0.16 A
0.16 A
1.1 A
0.51 A
0.3 A
0.22 A
0.21 A
0.6 A
0.33 A
0.24 A
0.23 A
0.5 A
Continuous output
1800 W
1800 W
2000 W
2300 W
2500 W
2500 W
2500 W
3000 W
3500 W
3500 W
3500 W
5000 W
1/2 hour rating
2200 W
2200 W
2200 W
2800 W
3000 W
3000 W
3000 W
3700 W
4100 W
4100 W
4100 W
6000 W
5 sec surge rating
5400 W
5400 W
6000 W
7000 W
7500 W
7500 W
7500 W
9000 W
10500 W
10500 W
10500 W
15000 W
Output voltage
230V
4%
Frequency
50Hz
0.1%
Waveshape
True Sinewave
Total harmonic distortion
<4%
Peak efficiency
94%
94%
90%
94%
94%
94%
94%
93%
94%
94%
95%
95%
Protection circuitry
overtemperature, overload / short circuit, battery undervoltage, battery overvoltage
Autostart sensitivity
0 - 20W adjustable
Power factor
All conditions
Height
3U
Depth
350 mm
Weight
16 kg
16 kg
22 kg
22 kg
22 kg
22 kg
22 kg
24 kg
24 kg
24 kg
24 kg
30 kg
1) Ratings at 25degC, nominal battery voltage and unity power factor.
2) Specifications subject to change without notice.
PAGE TOP